Voltage Drop Calculator

Calculate voltage drop in electrical wiring and check NEC compliance for your home projects

Calculate Voltage Drop

Voltage Drop

0 V
volts lost in wire

Percentage Drop

0%

Voltage at Load

0 V
voltage delivered

Wire Gauge Reference — Ampacity & Resistance

AWG Copper Ampacity Aluminum Ampacity Cu Ω/1000ft Al Ω/1000ft Common Uses
1415A3.145.17Lighting circuits, 15A outlets
1220A15A1.983.25General outlets, 20A circuits
1030A25A1.242.04Dryers, water heaters, 30A circuits
840A30A0.7781.28Ranges, large appliances
655A40A0.4910.808Subpanels, A/C units, EV chargers
470A55A0.3080.508Feeder circuits, large subpanels
385A65A0.2450.403Service entrance, large feeders
295A75A0.1940.319Service entrance, large feeders
1110A85A0.1540.253Service entrance, large feeders
1/0125A100A0.1220.201200A service, large feeders
2/0145A115A0.09670.159200A service entrance
3/0165A130A0.07660.126Large service entrance
4/0195A150A0.06080.100200A+ service entrance

Ampacity ratings based on NEC Table 310.16 for 60°C insulation (NM-B/UF-B). Actual ampacity depends on insulation type, ambient temperature, and conduit fill. Resistance values at 75°C.

When Voltage Drop Matters

Long wire runs to detached buildings

Running power to a detached garage, barn, or workshop 100+ feet from the main panel is the most common scenario where voltage drop becomes a problem. A 100-foot run on 12 AWG copper at 20A drops 3.96V (3.3%) — already over the 3% recommendation.

Outdoor & landscape lighting

Low-voltage landscape lighting runs can be very long. Even at 12V, a 200-foot run to garden lights can lose significant voltage, causing dim lights at the end of the run. Upsize wire or use a hub-and-spoke layout.

EV charger installations

Level 2 EV chargers draw 30-50A continuously for hours. At 40A on a 60-foot run, you need at least 6 AWG copper to stay under 3%. Many installations require 4 AWG for longer distances.

Well pumps & sump pumps

Motors are especially sensitive to low voltage. A well pump 200+ feet from the panel on undersized wire will overheat, lose efficiency, and fail prematurely. Always upsize wire for motor loads on long runs.

Pool & hot tub circuits

Pool pumps and hot tubs are often 50-100+ feet from the panel and draw significant current. The combination of distance and load makes voltage drop a critical consideration.

Solar panel & battery systems

DC circuits between solar panels, charge controllers, and batteries carry high current at low voltage. Even small resistance causes significant power loss — use the shortest, thickest wire practical.

How to Calculate Voltage Drop

Voltage drop occurs when electrical current flows through a wire's resistance, converting some energy to heat. The longer the wire and the higher the current, the more voltage is lost before reaching the load. The standard formula for single-phase circuits is:

VD = (2 × L × R × I) ÷ 1000

Where VD is voltage drop in volts, L is one-way length in feet, R is wire resistance in ohms per 1,000 feet, and I is current in amps. The factor of 2 accounts for the round-trip path (hot and neutral conductors). For three-phase circuits, replace 2 with 1.732 (√3).

NEC Voltage Drop Recommendations

The National Electrical Code (NEC) Section 210.19(A) recommends limiting voltage drop to 3% for branch circuits and 5% total from the service entrance to the farthest outlet. While these are recommendations rather than hard requirements, exceeding them can cause equipment damage, reduced efficiency, and safety issues.

For a 120V circuit, 3% equals 3.6V — meaning the minimum acceptable voltage at the outlet is 116.4V. For a 240V circuit, 3% equals 7.2V, so the minimum is 232.8V.

Copper vs. Aluminum Conductors

Copper wire has approximately 61% lower resistance than aluminum wire of the same gauge, resulting in significantly less voltage drop. However, aluminum is lighter and cheaper, making it popular for large service entrance cables and long feeder runs. When using aluminum, you typically need to upsize by two gauge sizes (e.g., use 2 AWG aluminum instead of 4 AWG copper) to achieve similar performance.

Frequently Asked Questions

What is an acceptable voltage drop for residential wiring?

The NEC recommends no more than 3% for branch circuits and 5% total from the service entrance. For a 120V circuit, that means keeping the drop under 3.6V on any single branch circuit.

How do I calculate voltage drop in a wire?

Use the formula VD = (2 × L × R × I) / 1000, where L is one-way length in feet, R is resistance in ohms per 1,000 feet, and I is current in amps. This calculator handles the math automatically for any wire gauge and material.

Does wire length affect voltage drop?

Yes, voltage drop increases proportionally with length. This is why long runs to detached buildings, outdoor lighting, and EV chargers often require upsizing the wire gauge beyond the minimum required for the circuit ampacity.

Is copper or aluminum better for reducing voltage drop?

Copper has lower resistance and less voltage drop for the same gauge. But aluminum can match copper's performance by going up two wire sizes, often at lower total cost for large runs.

What happens if voltage drop is too high?

Lights dim, motors overheat, electronics malfunction, and heaters underperform. Motors are especially vulnerable — low voltage increases current draw, which can burn out windings and drastically shorten motor life.

Related Calculators